Schrack circuit breaker 2P C20A

Schrack 20A circuit breaker (MCB), 2-pole with C tripping curve: the standard rating for socket circuits and dedicated circuits for a washing machine, tumble dryer or dishwasher in a Belgian home.

12.40 € 12.40 €

  • Merk
✓ Free shipping from €65 (BE) and €75 (NL) on standard items ✓ 14-day cooling-off period · terms and conditions
Merk: Schrack

In Belgian homes, a 20A circuit breaker (MCB) goes with 2.5 mm² cable. This Schrack BMS4 protects both conductors of the circuit and trips as soon as the current stays too high for too long or a short circuit occurs.

Use in the home

AREI (the Belgian electrical installation regulations) allows an MCB of up to 20 A on 2.5 mm² cable in homes. That is why you often see this rating on:

  • socket circuits in the living area, kitchen or bedrooms
  • a dedicated circuit for a washing machine, tumble dryer or dishwasher
  • an oven or an electric water heater

For washing machine, tumble dryer and dishwasher circuits, AREI also requires a 30 mA residual current device (RCD).

Benefits

  • two protected poles, suitable for both 3×230 V and 3N×400 V networks
  • C tripping curve: only trips magnetically at 5 to 10 times the rated current, so a motor starting up will not cause nuisance tripping
  • can be mounted in any position
  • flexible conductors can be connected using bootlace ferrules

Installation and connection

The MCB clips onto a standard DIN rail, alongside your other modular devices. Properly tightened terminals (2 to 2.4 Nm, according to Schrack) prevent connections from overheating. With the consumer unit cover fitted, it achieves IP40.

Good to know

Have the MCB installed by a qualified electrician, who will also decide which circuits are grouped on which RCD. After a new connection or an extension, the installation must be inspected by an approved inspection body.

Product codeBM417220 (Schrack BMS4 C 20/2)
EAN9004840390469
Rated current20 A
Tripping curveC
Poles2P, both poles protected
Breaking capacity4.5 kA (EN 60898-1), 6 kA (EN 60947-2)
Rated voltage230/400 V AC, 50/60 Hz
Width2 modules (approx. 35 mm)
Terminal capacity1 to 25 mm²
Power loss6.6 W
Max. back-up fuse80 A gG
Degree of protectionIP20, IP40 with cover
Ambient temperature-5 °C to +40 °C (calibrated at 30 °C)
StandardsEN 60898-1, EN 60947-2
Reference9004840390469
Category Circuit breakers and RCDs
Merk Schrack
Weight 0.24 kg

Shipping with GLS

  • We ship with GLS to your address in Belgium for €7.95; shipping is free when you spend €65 or more on standard items. To the Netherlands: €11.95, free from €75.
  • Items in stock are dispatched within 2 working days; GLS usually delivers the next working day. You will receive an email with the tracking code.
  • Collection in Tongeren-Borgloon is free: choose "Collection" at checkout and come by once you have received our message that your order is ready.
  • 14-day cooling-off period for consumers: return the item or bring it back to us. You may examine it as you would in a shop; if it has been used beyond that, we deduct the diminished value.

All about delivery & returns →

Your cart
Loading…