Schrack RCD 2P 30 mA 40A

Schrack BCF6 30mA residual current device (RCD), 2-pole, 40 A, Type A, for additional protection of people. AREI (the Belgian electrical installation regulations) requires 30 mA for the bathroom and for the washing machine and tumble dryer circuits, among others.

52.07 € 52.07 €

  • Merk
✓ Free shipping from €65 (BE) and €75 (NL) on standard items ✓ 14-day cooling-off period · terms and conditions
Merk: Schrack

A 30 mA residual current device (RCD) continuously compares the current flowing into a circuit with the current flowing back. If current leaks away, through a person or a faulty appliance, it switches off within a fraction of a second. This Schrack BCF6 does this for 2-pole circuits, with a rated current of 40 A.

Where do you install a 30 mA RCD?

AREI requires an additional RCD of no more than 30 mA for areas and circuits including:

  • the bathroom and shower room
  • the washing machine, tumble dryer and dishwasher circuits

It is installed downstream of the 300 mA main RCD. Other circuits that need extra protection, such as outdoor sockets, can also be connected to it.

Benefits

  • Type A: responds to AC and also to pulsating DC residual currents, such as those from appliances with electronics
  • trips at a leakage current between 15 and 30 mA: within 300 ms at 30 mA and within 40 ms at 150 mA
  • tripping independent of the mains voltage
  • test button so you can check for yourself that it works

Installation and connection

The BCF6 mounts on a 35 mm DIN rail to EN 60715, in any orientation you like. The supply can be connected at the top or the bottom. The terminals accept solid conductors from 1 to 35 mm² or flexible conductors up to 2 × 16 mm².

Good to know

An RCD does not protect against overload or short circuit; the circuit breakers downstream take care of that. Schrack recommends pressing the test button every month. Have the RCD installed by a qualified electrician; an inspection by an approved inspection body is then mandatory.

Product codeBC654203 (Schrack BCF6 40/2/003-A)
EAN9004840394047
Rated current40 A
Rated residual operating current (IΔn)30 mA
TypeA (AC and pulsating DC), no time delay
Poles2P
Rated voltage230 V AC, 50/60 Hz
Short-circuit withstand6 kA with back-up fuse of max. 63 A gG
Tripping timemax. 300 ms at 30 mA, max. 40 ms at 150 mA
Width2 modules (35 mm)
Terminal capacity1 to 35 mm² solid, 2 × 16 mm² flexible
Power loss5.8 W
Operating temperature-25 °C to +40 °C
StandardsEN 61008-1, EN 61008-2-1
Reference9004840394047
Category Circuit breakers and RCDs
Merk Schrack
Weight 0.22 kg

Shipping with GLS

  • We ship with GLS to your address in Belgium for €7.95; shipping is free when you spend €65 or more on standard items. To the Netherlands: €11.95, free from €75.
  • Items in stock are dispatched within 2 working days; GLS usually delivers the next working day. You will receive an email with the tracking code.
  • Collection in Tongeren-Borgloon is free: choose "Collection" at checkout and come by once you have received our message that your order is ready.
  • 14-day cooling-off period for consumers: return the item or bring it back to us. You may examine it as you would in a shop; if it has been used beyond that, we deduct the diminished value.

All about delivery & returns →

Your cart
Loading…